Date:05-09-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:0800555SYSTEM NAME:GASQUET C.S.D.COUNTY:DEL NORTE 
SOURCE NO.:901SOURCE NAME:DBP-1125...*SOURCE CLASS:DBPASTATUS:A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2943 BROMODICHLOROMETHANE 7.500 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2942 BROMOFORM < 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2941 CHLOROFORM 33.000 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2454 DIBROMOACETIC ACID < 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2944 DIBROMOCHLOROMETHANE 1.200 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2451 DICHLOROACETIC ACID 11.000 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2456 TOTAL HALOACETIC ACIDS (HAA5) 25.000 6.000 UG/L 60 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2453 MONOBROMOACETIC ACID < 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2450 MONOCHLOROACETIC ACID < 2.000 UG/L 2 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2950 TTHM 41.000 4.000 UG/L 80 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2452 TRICHLOROACETIC ACID 14.000 1.000 UG/L 1 10-12-2023 12 2024/10
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

*Please refer to the Stage 2 DBP Monitoring Plan Approval Letter for full sample point names.
RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)